Insulation Thickness Calculator
Find how thick each insulation material must be to reach a target U-value, or to match an existing layer, and see how much space a vacuum insulation panel (VIP) saves.
Next step
Send us the thickness and the panel area or drawing. We propose VIP series, panel sizes and layout.
Request a panel layout Compare the five VIP series
Last updated:
How the calculation works
An insulation layer adds thermal resistance R. Its thickness is d = λ × R, where λ is the material’s thermal conductivity. Halve λ and the layer needs half the thickness.
To reach a target U-value, the layer must add R = 1/Utarget − 1/Uexisting. Without an existing U-value, the calculator subtracts only the surface resistances of a wall, 0.17 m²·K/W (ISO 6946).
To match an existing layer, the calculator takes that layer’s resistance (thickness ÷ λ) and finds the thickness of every other material with the same resistance.
Which VIP value should you use?
VIP data sheets state the conductivity at the centre of a new panel. Over its service life, gas and water vapour slowly enter the envelope, and the barrier film carries some heat around the panel edges. A wall built from many panels therefore performs below the centre-of-panel value.
For building walls, roofs and floors, use the design value. IEA EBC Annex 39 cites a Swiss design value of 8 mW/(m·K) at the centre of a VIP with a metallized film envelope, allowing for about 25 years of moisture and air ingress. Panel edges come on top: for a 1.00 × 0.50 × 0.02 m panel the same report gives an effective value of about 8.7 mW/(m·K), and smaller panels or metal-foil envelopes lose more. The calculator uses 8 mW/(m·K); for a specific panel layout, add the edge effect or ask us to calculate it. The declared values are useful for comparing panels and for appliances and cold-chain equipment with large panels and controlled conditions.
Worked examples
| Case | Thickness needed |
|---|---|
| Interior insulation of a solid masonry wallExisting wall U ≈ 1.4 → target 0.24 W/(m²·K). Every millimetre is lost room depth. |
|
| Roof terrace or balcony over a heated roomExisting slab U ≈ 1.0 → target 0.15 W/(m²·K). Door thresholds limit the build-up height. |
|
| Cold room or freezer wall replacing 100 mm PUSame layer resistance as 100 mm PU foam; the space gained becomes storage volume. |
|
| Appliance cabinet wall replacing 60 mm PUCentre-of-panel values; real cabinets combine VIP with foam and lose some resistance at joints. |
|
Conductivity values used
| Material | Typical range, mW/(m·K) | λ used, mW/(m·K) | Basis |
|---|---|---|---|
| VIP, building design value | ≈ 8 | 8 | Aged centre-of-panel value for metallized-film VIPs over 25 years (IEA EBC Annex 39); panel edges not included |
| Supertech fumed silica VIP | ≤ 4.5 | 4.5 | Declared initial centre-of-panel value; for appliances and cold-chain equipment |
| Supertech fiberglass VIP | 2.0 ± 0.5 | 2 | Declared initial centre-of-panel value (Double Alu); for appliances and cold-chain equipment |
| PU / PIR foam | 20–25 | 22 | Typical value |
| XPS | 30–35 | 32 | Typical value |
| EPS | 33–38 | 35 | Typical value |
| Mineral / rock wool | 35–45 | 40 | Typical value |
What this calculator does not check
- Moisture. Interior insulation changes where condensation can form. Check the build-up with a hygrothermal assessment before installing.
- Thermal bridges. VIP panel edges and joints, fixings, frames, slab edges and window reveals add heat loss that a one-dimensional calculation does not see.
- Pipes and curved surfaces. The calculation is for flat layers; pipe insulation needs the cylindrical formula.
- Regulations and fire. Required U-values and fire classes depend on the country and building type.