VIP in Cold Room Walls: Panel Position and Ageing

Welded edge of a stainless-steel M-VIP. The product photograph does not show a cold room installation or measure ageing.
Welded edge of a stainless-steel M-VIP. The product photograph does not show a cold room installation or measure ageing.

In cold room and freezer walls, a vacuum insulation panel (VIP) usually sits inside a polyurethane (PU) or PIR layer rather than replacing it. Two published findings point in different directions: tests favour the VIP on the ambient side, while field data show VIPs age more slowly when they are cold. The panel temperature in the chosen layer order decides how much of each benefit you get.

Why do cold room walls combine VIP with PU foam?

A VIP supplies most of the thermal resistance in a thin layer, but it cannot be cut, drilled or fixed through on site. Foam around it fills joints, protects the envelope, carries fixings and forms the panel skin bond. The usual question is therefore not VIP or PU, but where the VIP goes within the wall build-up.

Which side of a cold room wall should the VIP face?

Kan et al. (2021) built three test chambers of the same 300 × 300 × 300 mm outer size, each with a 10 mm VIP layer and a 10 mm PU layer, and placed the VIP on the inside, in the middle or on the outside. Numerical and physical models agreed that the VIP on the ambient side, where temperature fluctuates, gave the best overall insulation for holding the chamber temperature. A 2025 simulation of 20 ft marine reefer envelopes by Kan et al. also found external VIP placement best, with up to about 3.66 kg less CO₂ than a conventional PU envelope over 24 hours.

Both studies concern small chambers or simulated container walls under fluctuating outside conditions. They describe delay and damping of temperature swings, not the annual electricity use of a full cold store.

Does layer order change the U-value of a cold room wall?

Not in steady state. Thermal resistances in series add up in any order, so a VIP + PU wall has the same U-value whether the VIP faces in or out. Layer order matters for transient behaviour (sun, door openings, defrost and daily ambient swings) and for the temperature each layer operates at.

Does a VIP age more slowly in a cold room?

Yes, according to the available field data. Brunner, Ghazi Wakili and Johansson (2013) tracked VIP internal pressure for five years in a supermarket refrigerator room and freezer room. The pressure rose roughly linearly by about 0.6 mbar per year in the refrigerator room and by 0.10–0.26 mbar per year in the freezer room, depending on panel type; the authors conclude that ageing decelerates compared with standard test conditions.

For scale, the preliminary Swiss approval rules reported in IEA EBC Annex 39 asked for a pressure increase below 2 mbar per year at 23 °C and 50% RH for a 50 × 50 × 2 cm panel. Gas and water vapour permeation through the barrier is temperature-activated, which is why the same panel loses vacuum more slowly at low temperature (Simmler & Brunner, 2005).

How hot does the VIP get on the ambient side?

Hypothetical wall: 30 °C outside, −20 °C room, 10 mm VIP at 0.005 W/(m·K) and 80 mm PU at 0.022 W/(m·K), with ISO 6946 surface resistances of 0.04 (outside) and 0.13 m²·K/W (inside). Only the layer order changes.

VIP positionWarm faceCold faceMean panel temperature
Outside of the PU (ambient side)29.7 °C12.4 °C21.0 °C
Inside of the PU (room side)−1.7 °C−18.9 °C−10.3 °C

The heat flow through both walls is the same, but the outer VIP works near ambient temperature while the inner VIP works near the room temperature. The low-temperature ageing benefit measured in refrigerator and freezer rooms therefore applies mainly to the room-side layout. If an ambient-side layout is chosen for its dynamic advantage, judge service life from ageing data at the warmer panel temperature, including sun-exposed walls and loading docks.

What does a metal envelope change in a cold room?

A stainless-steel M-VIP encloses the core in a welded metal shell instead of a film. The shell changes mechanical behaviour, but it is not puncture-proof and does not establish unlimited life: welds, core and gas control still need ageing evidence. Supertech’s stainless M-VIP brochure states a recommended range of −196 to +800 °C and a conductivity of ≤ 2.0 mW/(m·K) at 25 °C; that value is not a cold-temperature figure. Panel sizes run from 100 × 100 to 500 × 1000 mm, so a cold room wall has many joints, and the metal edge is a thermal bridge that belongs in the effective-value calculation.

What should a cold room VIP specification include?

Frequently asked questions about VIP in cold rooms

Can the freezer-room pressure rise be used as a VIP lifetime?

No. The 0.10–0.26 mbar per year values describe specific panels in one supermarket freezer room over five years. Lifetime also depends on the end-of-life criterion, panel size, envelope, humidity and the temperature at the panel.

Is the VIP on the ambient side always the better choice?

It performed best in the published small-chamber test and reefer simulation for damping outside fluctuations. It also runs the panel warmer, which speeds ageing and makes the panel easier to damage if it is near the outer skin. Compare both effects for the project.

Can VIP panels be cut to fit a cold room on site?

No. Cutting or drilling breaks the vacuum. Panels are made to a layout drawing, and the remaining gaps are filled with foam.

Plan the VIP layout with the panel temperature in mind

Send the wall build-up, room set-point, outside conditions and available thickness. Ask for the calculated panel temperatures for each layer order and for ageing data that match them.

References

Need engineering data for your project?

Our team answers technical questions about vacuum insulation with test data, not marketing claims. Ask us directly.

Request a Quote