Metal VIP in Opaque Insulating Glass: What a Façade Spandrel Can Achieve
Key facts: metal VIP in opaque insulating glass
- An opaque insulating glass module places a vacuum insulation panel in the cavity of an insulating glass unit, so spandrels and slab edges look like the vision glass but insulate like a thick wall.
- Supertech stainless-steel M-VIP reaches ≤ 2.0 mW/(m·K) at 25 °C. A 20 mm panel gives about 10 m²·K/W at the centre of the panel, the thermal resistance of roughly 35–50 mm of a typical fumed-silica film VIP.
- The configuration with a ceramic-fibre core is classified A1 (non-combustible) to EN 13501-1 by SGS.
- The welded stainless-steel envelope contains no polymer barrier film, resists puncture during assembly and is stated at a leakage rate below 10⁻¹⁰ Pa·m³/s.
- Cores: ceramic fibre, glass fibre or fumed silica. Five standard formats from 286 × 286 to 806 × 606 mm; other sizes are made with dedicated tooling.
- The module value depends on edges and joints: plan the panel layout and declare a whole-module U-value, not a centre-of-panel figure.
What is an opaque insulating glass module?
Curtain walls and glazed façades have zones where daylight is neither needed nor wanted: in front of floor slabs, at spandrels between windows and along parapets and edges. Traditionally these areas use a shadow box or a back-panel with mineral wool, which needs depth and often looks different from the vision glass next to it.
An opaque insulating glass module solves both problems. It is built like an insulating glass unit, but its cavity is filled with a vacuum insulation panel. Because the module is glazed into the same frame or structural-glazing system as the vision units, the façade stays visually continuous and the opaque zone needs no separate wall construction.
The typical build-up, from outside to inside:
- Outer pane of thermally toughened (tempered) glass; type and thickness follow the structural design.
- Cavity containing the VIP and a design layer directly behind the outer pane: glass-fibre fleece, metal mesh or a digitally printed layer sets the colour and texture seen from outside.
- Inner pane of float or tempered glass, or alternatively a 3 mm aluminium sheet, anodised or powder-coated, as the room-side face.
- A hermetic edge seal around the perimeter, as in any insulating glass unit.
The module is always opaque, with no light transmission, and is used wherever the façade needs insulation instead of a view.
Why a metal-envelope VIP suits the insulating glass cavity
Most VIPs are wrapped in a multilayer polymer film with a metallised or aluminium barrier. Inside an insulating glass unit the panel is sealed for the life of the façade and cannot be inspected or replaced, so how the envelope behaves over decades matters more than in most other uses. A welded stainless-steel envelope changes four things:
- Vacuum retention. Gas enters a VIP mainly through its envelope. A continuous welded steel shell blocks permeation through the faces; the stainless-steel M-VIP brochure states a leakage rate below 10⁻¹⁰ Pa·m³/s.
- No organic barrier layers. Inserts in an insulating glass cavity must not release volatile substances that could fog the inside of the glass. A steel shell with an inorganic core contains no laminating adhesives or polymer films. The complete insert still needs a fogging test in the cavity build-up.
- Robust handling. Glass processing involves cutting, handling, pressing and sealing. A 0.1 mm stainless-steel face is far less vulnerable to puncture than a film envelope, and a punctured VIP loses most of its insulating value.
- Fire behaviour. The tested ceramic-fibre configuration is non-combustible (A1). This is relevant wherever façade rules require non-combustible materials in the external wall.
How film and metal envelopes differ in construction is explained in What Is a Metal Vacuum Insulation Panel?
Thermal values a stainless-steel M-VIP can achieve in the opaque module
| Aspect | Value | Basis |
|---|---|---|
| Thermal conductivity | ≤ 2.0 mW/(m·K) at 25 °C | Stainless-steel M-VIP brochure configuration |
| Centre-of-panel thermal resistance | ≈ 10 m²·K/W at 20 mm; ≈ 15 m²·K/W at 30 mm | R = d ÷ λ |
| Centre-of-panel U-value of the module | ≈ 0.10 W/(m²·K) at 20 mm; ≈ 0.066 W/(m²·K) at 30 mm | Calculated with two 8 mm panes and surface resistances of 0.13 + 0.04 m²·K/W |
| Reaction to fire | Class A1 | SGS report XMIN2512002899CM01: 0.1 mm stainless-steel faces, ceramic-fibre core |
| Envelope leakage rate | < 10⁻¹⁰ Pa·m³/s | Stated in the stainless-steel M-VIP brochure |
| Panel thickness | 10–30 mm standard formats; 2–40 mm product range | Standard size list and brochure |
| Areal mass | 2–5 kg/m² at 10 mm | Brochure; glass adds about 2.5 kg/m² per mm of thickness |
Thinner modules at the same insulation level. Thermal resistance is thickness divided by conductivity. Film-wrapped fumed-silica VIPs typically reach 3.5–5 mW/(m·K), so they need about 35–50 mm to match the centre-of-panel resistance of a 20 mm stainless-steel M-VIP. The saved depth can go into a slimmer façade or into extra insulation within the same cavity. The method is explained in our insulation thickness guide.
Weight stays dominated by the glass. Two 6 mm panes weigh about 30 kg/m². The M-VIP adds a moderate share on top, which keeps the module within the handling range of normal insulating glass.
M-VIP core options: ceramic fibre, glass fibre or fumed silica
The stainless-steel envelope can be combined with three inorganic cores. They differ in starting conductivity, in how they respond to a rise in internal pressure over time, and in temperature resistance. The trends below are typical for each core family:
| Core | Strength | Consider | Good fit |
|---|---|---|---|
| Ceramic fibre | Inorganic fibre for high temperatures; tested configuration classified A1 | Fibre cores respond to a rise in internal pressure | Projects led by a non-combustibility requirement |
| Glass fibre | Lowest starting conductivity of the three | Most sensitive to internal pressure; relies on envelope tightness and getter | Slimmest modules for a given thermal target |
| Fumed silica | Fine pore structure; tolerates pressure rise best | Higher starting conductivity, so more thickness for the same resistance | Long design lives where stability matters most |
The ≤ 2.0 mW/(m·K) value belongs to the brochure configuration and should not be transferred to every core. The differences between fibre and particle cores are explained in Fumed Silica vs. Fiberglass VIP Cores.
Standard M-VIP sizes and custom formats
Five rectangular formats are available as standard:
| Length × width, mm | Thickness, mm | Edge length per m² of panel |
|---|---|---|
| 286 × 286 | 10, 15, 20 | ≈ 14.0 m |
| 406 × 206 | 10, 15, 20, 25, 30 | ≈ 14.6 m |
| 606 × 306 | 10, 15, 20, 25, 30 | ≈ 9.8 m |
| 606 × 406 | 10, 15, 20, 25, 30 | ≈ 8.2 m |
| 806 × 606 | 10, 15, 20, 25, 30 | ≈ 5.8 m |
Other sizes are made to order. Because the stainless-steel shell is formed in a die, each new size requires its own tooling. For façade projects this is often worthwhile: a panel sized to the module grid reduces joints, and the edge length per square metre falls as the panel gets larger.
From centre-of-panel value to module U-value: edges and joints
A centre-of-panel value describes only the middle of the panel. Inside the module, two further heat paths matter:
- The envelope edge. Steel conducts heat far better than the evacuated core. Where the shell turns around the panel edge, heat bypasses part of the vacuum. The effect is described per metre of edge and grows with the edge length in the module.
- Joints between panels. Where several panels fill one module, the gaps and sealing flanges between them are not vacuum-insulated.
Together these losses can take away a significant part of the centre-of-panel advantage if the layout is left to chance. Four measures keep them small:
- Use the largest practical panel. Choose the 806 × 606 mm format or a custom size matched to the module, so each module contains as few panels as possible.
- Stagger the joints. Two thinner layers with offset joints place a vacuum core behind every edge of the other layer.
- Detail the flanges. Orient and fold the sealing flanges so that the gaps between cores stay narrow.
- Declare the module value. Calculate the module U-value with a numerical thermal-bridge model, or measure it, and specify that value to the façade engineer.
Why edge heat flow and edge gas leakage are separate questions is covered in VIP Edge Leakage vs. Thermal Bridges.
What to define for an opaque insulating glass project
- Module sizes and quantities, so the panel layout and any custom tooling can be decided early.
- Target module U-value and the calculation or test method that will prove it.
- Fire requirement for the external wall, which decides whether the A1-classified ceramic-fibre configuration is needed.
- Design life and climate, which guide the choice between fibre and fumed-silica cores.
- Glass build-up and back face: pane types and thicknesses, inner glass or aluminium sheet, and the design layer.
- Cavity compatibility: fogging test and edge-seal compatibility for the complete insert.
Product data are on the VAP Metal VIP page, and the stainless-steel M-VIP data sheet can be requested from our technical resources.
Frequently asked questions
What is an opaque insulating glass module with a VIP?
It is an insulating glass unit whose cavity is filled with a vacuum insulation panel instead of air or gas. A tempered outer pane faces the weather, a design layer behind it sets the appearance, and the VIP provides the insulation. The back is either an inner glass pane or a 3 mm aluminium sheet. The module is glazed into the same façade system as the vision glass and is used where no daylight is needed, such as spandrels, slab edges and parapets.
How well does a stainless-steel M-VIP insulate inside the module?
At 25 °C the brochure configuration of Supertech stainless-steel M-VIP has a thermal conductivity of ≤ 2.0 mW/(m·K). A 20 mm panel therefore has a centre-of-panel thermal resistance of about 10 m²·K/W, and a 30 mm panel about 15 m²·K/W. With two glass panes and standard surface resistances this corresponds to a centre-of-panel U-value of roughly 0.10 and 0.066 W/(m²·K). Edges and joints between panels add heat flow, so the U-value of the whole module must be calculated or tested for the actual layout.
Is the stainless-steel M-VIP non-combustible?
The configuration with 0.1 mm stainless-steel faces and a ceramic-fibre core was classified A1 to EN 13501-1:2018 by SGS (report XMIN2512002899CM01, January 2026), based on EN ISO 1182 and EN ISO 1716 tests. Configurations with glass-fibre or fumed-silica cores are separate products and need their own classification.
Which core should I choose for a façade module?
Glass-fibre cores give the lowest starting conductivity but are the most sensitive to any rise in internal pressure. Fumed-silica cores start higher but tolerate pressure rise best, which favours long service lives. Ceramic-fibre cores suit higher temperatures and are the configuration with the A1 classification. The choice depends on the thermal target, fire requirement and design life of the project.
Can panels be made in sizes other than the standard formats?
Yes. Five standard formats from 286 × 286 mm to 806 × 606 mm are available in 10–30 mm thickness. Other sizes are made to order; because the stainless-steel shell is formed in a die, a new size requires dedicated tooling. Fix the module grid early so the tooling decision can be made with the façade design.
References
- SGS-CSTC Standards Technical Services, Xiamen Branch — Test report XMIN2512002899CM01, Metal VIP, reaction-to-fire classification A1, issued 14 January 2026.
- EN 13501-1:2018 — Fire classification of construction products and building elements. Classification using data from reaction to fire tests.
- EN ISO 1182 — Reaction to fire tests for products. Non-combustibility test. EN ISO 1716 — Determination of the gross heat of combustion.
- EN 1279 series — Glass in building. Insulating glass units (Part 4: edge seals and inserts, including fogging).
- EN 673 — Glass in building. Determination of thermal transmittance (U value). Calculation method.
- EN ISO 10211 — Thermal bridges in building construction. Heat flows and surface temperatures. Detailed calculations.
- EN 17140 — Thermal insulation products for buildings. Factory-made vacuum insulation panels (VIP). Specification.
Related: VAP Metal VIP · Stainless Steel VIP in Building Insulation · What Is an M-VIP? · Discuss your façade project